Hi Jim,

an addition to what Ben wrote. Make sure that you wrote the symbol of a
Siemens value correct. Some versions of Siemens TIA Variable mappings
require the ["]-Symbol included. So your path could also be required to
escape those.
In your case this could be something like:
builder.addItem("S7PLC.CureAbort", "ns=2;s=\"S7PLC\".CureAbort:BOOL", true);
As far as i worked with it correlates with the structure of your project
and your modularization in Components and FunctionBlocks but this is not
consistent over all used PLC or Sinumerik Controls.

Greetings Matthias


Am Do., 11. März 2021 um 15:29 Uhr schrieb Wang, Jim <
Jim.Wang@westpharma.com>:

> Hi PLC4X team,
>
> When I use PLC4X's OPCUA protocol to write PLC, I always get ACCESS_DENIED
> for the PLC's tag (Reading is OK.)
> I list my code and message I get below in FYI: sections.
> How can I get rid of this issue?
> Thanks,
>
> Jim
>
>
> FYI: my codes
> ==================================
>        public static void WritePLC(PlcConnection plcConnection) throws
> InterruptedException, Exception, TimeoutException {
>               PlcWriteRequest.Builder builder =
> plcConnection.writeRequestBuilder();
>               builder.addItem("S7PLC.CureAbort", "ns=2;s=
> S7PLC.CureAbort:BOOL", true);
>               PlcWriteRequest writeRequest = builder.build();
>               PlcWriteResponse response = writeRequest.execute().get();
>               for (String fieldName : response.getFieldNames()) {
>                   if(response.getResponseCode(fieldName) ==
> PlcResponseCode.OK) {
>                      System.out.println("Value[" + fieldName + "]:
> updated");
>                   }
>                   else {
>                      System.out.println("Error[" + fieldName + "]: " +
> response.getResponseCode(fieldName).name());
>                   }
>               }
>        }
>
> FYI: the message when I run my codees
> ======================================
> opcua:tcp://localhost:49601/
> [main] INFO org.apache.plc4x.java.PlcDriverManager - Instantiating new PLC
> Driver Manager with class loader
> jdk.internal.loader.ClassLoaders$AppClassLoader@443b7951<mailto:
> jdk.internal.loader.ClassLoaders$AppClassLoader@443b7951>
> [main] INFO org.apache.plc4x.java.PlcDriverManager - Registering available
> drivers...
> [main] INFO org.apache.plc4x.java.PlcDriverManager - Registering driver
> for Protocol s7 (Siemens S7 (Basic))
> [main] INFO org.apache.plc4x.java.PlcDriverManager - Registering driver
> for Protocol opcua (OPC UA (TCP))
> [main] INFO org.apache.plc4x.java.opcua.connection.OpcuaTcpPlcConnection -
> Configured OpcuaTcpPlcConnection with: host-name 127.0.0.1
> [NonceUtilSecureRandom] INFO
> org.eclipse.milo.opcua.stack.core.util.NonceUtil - SecureRandom seeded in
> 0ms.
> [main] INFO org.eclipse.milo.opcua.sdk.client.OpcUaClient - Eclipse Milo
> OPC UA Stack version: 0.5.3
> [main] INFO org.eclipse.milo.opcua.sdk.client.OpcUaClient - Eclipse Milo
> OPC UA Client SDK version: 0.5.3
> Error[S7PLC.CureAbort]: ACCESS_DENIED
> Find West on Twitter <http://twitter.com/#!/WestPharma> and LinkedIn<
> http://www.linkedin.com/company/west-pharmaceutical-services?trk=fc_badge
> >.
>
> ________________________________
> The contents of this message are confidential and may be privileged. If
> you have received this message in error, please permanently delete it,
> along with any files that may be attached to this message, without reading,
> printing, copying, forwarding or otherwise distributing it. Please notify
> the sender of the error immediately so that we can prevent it from
> happening again.
>
>

Mime
  • Unnamed multipart/alternative (inline, None, 0 bytes)
View raw message